Server Installation

1 ESD Safety​

1.1 General Anti-Static Operation Specifications​

Electrostatic discharge from the human body can easily break down electrostatic-sensitive components such as the server motherboard and storage devices. Before performing any hardware assembly, rack mounting, or disassembly operations, the following specifications must be observed:

  1. Data center environment requirements

    • Lay anti-static flooring/mats in the data center, with matching anti-static work chairs; the partitions and curtains in the data center must be made of anti-static materials.
    • The metal enclosures of cabinets and racks, as well as floor-standing equipment, must be reliably grounded; instruments on the workbench must be connected to a common grounding terminal.
    • Maintain reasonable temperature and humidity in the data center; a dry environment greatly increases the probability of static electricity generation.
  2. Personnel operation requirements

    • Before operating, remove conductive items such as watches, necklaces, and metal jewelry, and wear anti-static work clothes.
    • When touching components such as boards and hard drives, anti-static wrist straps / anti-static gloves must be worn.

    ESD Prohibited Conductive Objects Diagram

  3. Material storage and handling

    • Unassembled components must be stored in anti-static packaging bags / anti-static boxes at all times.
    • Temporarily removed hardware must be placed on anti-static foam pads.
  4. Hardware touching prohibitions

    • Do not directly touch circuit board solder joints, chip pins, or exposed gold finger areas.

1.2 Steps for Wearing the Anti-Static Wrist Strap​

Before operating, confirm that the cabinet has been reliably grounded:

  1. Insert the wrist into the anti-static wrist strap;

    ESD Wrist Strap Wearing Diagram

  2. Tighten the buckle so that the inner side of the strap fully fits the skin;

  3. Insert the grounding plug of the wrist strap into the ESD grounding jack of the cabinet.

2 Required Installation Tools​

Before performing physical installation and disassembly of the server, prepare the following tools and protective materials in advance:

  • Protection: anti-static wrist strap, anti-static gloves, anti-static packaging bags, work gloves
  • Tools: M3 Phillips screwdriver, flat-head screwdriver

3 Installation Environment​

3.1 Space and Ventilation Requirements​

To ensure heat dissipation and later maintenance, data center deployment must meet the following conditions:

  • The server may only be installed in a restricted-access area.
  • Keep the area around the equipment clean and free of debris.
  • Reserve ≥800 mm of maintenance and heat dissipation space in front of and behind the cabinet.
  • The server air intakes must not be blocked to ensure smooth ventilation.
  • The air supply volume of the data center air conditioning must meet the heat dissipation requirements of the whole server.

3.2 Temperature and Humidity Standards​

The equipment must be placed in a data center with controlled temperature and humidity, equipped year-round with temperature control and humidification/dehumidification equipment. The parameter standards are as follows:

ItemOperating Standard
Temperature5 ℃ to 40 ℃ (41 ℉ to 104 ℉)
Humidity8% RH to 90% RH (non-condensing)

3.3 Cabinet Compatibility Requirements​

  • The cabinet must comply with the IEC 297 standard, be a 19-inch standard rack, and have a cabinet depth ≥800 mm.
  • The front door of the cabinet must be equipped with a dust filter.
  • Reserve an AC power inlet position at the rear of the cabinet.